4 CORE – Copper XLPE Armoured & Unarmoured Power Cables

Type No. of
cores &
cross
sectional area
mm2
Min No.
of Wires
Thickness
of XLPE
Insulation
(Nom.) mm
Min. Thickness of PVC inner sheath mm
Nominal
Dimensions of Armour
Strip
mm
Wire
mm
Min. Thickness of
PVC Outer Sheath
Strip
mm
Wire
mm
Overall Diameter
(Approx.)
Strip
mm
Wire
mm
Approx. Net Wt.
of Cable
Strip
(Kg/Km)
Wire
(Kg/Km)
Max. D.C.
Resistance
at 20OC
Ohms/Km
Max. A.C.
Resistance
at 90OC
Ohms/Km
Approx.
Resistance
at 50 Hz
Ohms/Km
Approx.
Capacitance
mFd/Km
CURRENT RATINGS
Direct in Ground Amps In Air Amps
2XWY/2XFY 4C X 16 6 0.70 0.3 4×0.8 1.60 1.40 1.40 22.8 21.2 1249 1026 1.15 1.47 0.080 0.36 92 79
2XWY/2XFY 4C X 25 6 0.90 0.3 4×0.8 1.60 1.40 1.40 23.8 22.2 1645 1406 0.727 0.930 0.080 0.20 119 108
2XWY/2XFY 4C X 35 6 0.90 0.3 4×0.8 1.60 1.40 1.40 26.0 24.4 2070 1816 0.524 0.671 0.080 0.23 144 132
2XWY/2XFY 4C X 50 6 1.00 0.3 4×0.8 1.60 1.56 1.56 29.5 27.9 2676 2375 0.387 0.495 0.078 0.24 174 162
2XWY/2XFY 4C X 70 12 1.10 0.4 4×0.8 2.00 1.56 1.56 34.1 31.7 3791 3259 0.268 0.343 0.077 0.26 210 198
2XWY/2XFY 4C X 95 15 1.10 0.4 4×0.8 2.00 1.72 1.56 37.9 35.2 4938 4308 0.193 0.247 0.074 0.29 252 240
2XWY/2XFY 4C X 120 18 1.20 0.5 4×0.8 2.00 1.88 1.72 41.9 39.1 6042 5362 0.153 0.196 0.072 0.29 288 276
2XWY/2XFY 4C X 150 18 1.40 0.5 4×0.8 2.50 2.04 1.88 46.3 42.6 7611 6517 0.124 0.159 0.072 0.29 324 318
2XWY/2XFY 4C X 185 30 1.60 0.5 4×0.8 2.50 2.20 2.04 51.5 47.8 9298 8079 0.0991 0.127 0.072 0.29 360 366
2XWY/2XFY 4C X 240 34 1.70 0.6 4×0.8 2.50 2.36 2.20 57.5 53.8 11794 10423 0.0754 0.0965 0.072 0.31 414 426
2XWY/2XFY 4C X 300 34 1.80 0.7 4×0.8 3.15 2.52 2.36 64.5 59.5 15019 12895 0.0601 0.0769 0.071 0.33 462 480
2XWY/2XFY 4C X 400 53 2.00 0.7 4×0.8 3.15 2.84 2.68 72.1 67.1 18752 16352 0.0470 0.0602 0.070 0.33 510 546
Type No. of
cores &
cross
sectional area
mm2
Min No.
of Wires
Thickness
of XLPE
Insulation
(Nom.) mm
Min. Thickness of PVC inner sheath mm Nominal
Thickness of PVC Outer sheath mm
Overall
Diameter
(Approx)
mm
Approx.
Net Wt.
of Cable
Kg/Km
Max. DC
Resistance
at 20OC
Ohms/Km
Max. AC
Resistance
at 90OC
Ohms/Km
Approx.
Reactance
at 50 HZ
Ohm/Km
Approx.
Capacitance
mFd/Km
CURRENT RATINGS
Direct in Ground Amps In Air Amps
2XY 4C X 16 6 0.70 0.3 1.80 21.0 843 1.15 1.47 0.080 0.36 92 79
2XY 4C X 25 6 0.90 0.3 2.00 22.4 1232 0.727 0.930 0.080 0.20 119 108
2XY 4C X 35 6 0.90 0.3 2.00 24.6 1620 0.524 0.671 0.080 0.23 144 132
2XY 4C X 50 6 1.00 0.3 2.00 27.8 2125 0.387 0.495 0.078 0.24 174 162
2XY 4C X 70 12 1.10 0.4 2.20 32.0 3000 0.268 0.343 0.077 0.26 210 198
2XY 4C X 95 15 1.10 0.4 2.20 35.5 4013 0.193 0.247 0.074 0.29 252 240
2XY 4C X 120 18 1.20 0.5 2.40 39.5 5043 0.153 0.196 0.072 0.29 288 276
2XY 4C X 150 18 1.40 0.5 2.60 43.0 6176 0.124 0.159 0.072 0.29 324 318
2XY 4C X 185 30 1.60 0.5 2.80 48.3 7701 0.0991 0.127 0.072 0.29 360 366
2XY 4C X 240 34 1.70 0.6 3.00 54.6 10037 0.0754 0.0965 0.072 0.31 414 426
2XY 4C X 300 34 1.80 0.7 3.20 60.6 12513 0.0601 0.0769 0.071 0.33 462 480
2XY 4C X 400 53 2.00 0.7 3.60 68.3 15945 0.0470 0.0602 0.070 0.33 510 546